The size you need is determined by two numbers: your running watts and your starting watts. Add up what you must keep powered, then size the generator at or above the largest starting surge while it still covers total running load. Most homes land between 5,500 and 7,500 running watts for essential circuits, and 12,000 to 22,000 watts for whole-house coverage.
The single most common sizing mistake isn't picking a unit that's too small β it's adding up nameplate watts and assuming the generator must cover the sum. Start-up surges, not steady draw, set the floor for a portable unit, and transfer-switch capacity, not generator output, sets the ceiling for a whole-house install. Get those two facts straight and the selection narrows to a handful of models.
Why running watts and starting watts decide the size before anything else
Running watts is the power a device draws continuously once it's operating. Starting watts is the brief spike a motor pulls in its first second or two β typically two to three times running watts for compressors and pumps. A generator must clear the highest starting surge while also carrying every other load that's running at the same moment.
The governing document for this arithmetic is the National Electrical Code, Article 220, which sets load-calculation methods for dwellings, and Article 702, which covers optional standby systems. The code doesn't tell you which generator to buy, but it does define how connected load is computed, and local inspectors apply it. That matters because a permit-driven installation will be reviewed against those methods, not against a sales brochure.
Compressor-driven appliances carry the worst surges. A central air conditioner rated at 3,500 running watts may demand 8,000 to 10,000 watts for a second or two. A well pump at 1,000 running watts can spike to 2,000β3,000. Resistive loads β space heaters, incandescent lighting, a coffee maker β have essentially no surge and can be added arithmetically.
Gas-fired equipment needs a separate calculation because its draw is small but non-negotiable. A modern condensing furnace blower motor typically runs 400β800 watts. A tankless gas water heater's electric draw depends entirely on model β many need 120 volts for controls only, while some larger units require more. Check the data plate; do not assume.
The load worksheet: add your circuits in this order
Work from the circuits you'd actually keep alive, not from the square footage of the house. Square footage drives central air sizing, which drives the biggest single number in the calculation β but it doesn't tell you what you personally need backed up.
Start with the non-negotiable loads: refrigerator (about 600β800 running watts for a typical 2020s unit, with a 1,200-watt surge), furnace blower, sump pump, well pump, and a few LED lights and phone chargers. That baseline usually totals 1,500β2,500 running watts. Add a window air conditioner and you're near 3,000. Add a central system and you're at 6,000β8,000.
Then apply the surge rule. Identify the single largest starting load and confirm the generator's surge rating exceeds it. Locked-rotor amps stamped on the motor nameplate, multiplied by voltage, gives the worst-case figure β that's the number a soft-start kit is designed to reduce, often by 30β50% on a residential condenser.
| Load | Running watts | Typical starting watts | Notes |
|---|---|---|---|
| Refrigerator (2020s, 18β22 cu ft) | 600β800 | 1,200 | Surge lasts 1β2 seconds |
| Gas furnace blower | 400β800 | 1,200 | ECM motors surge less than PSC |
| Sump pump (1/3 hp) | 800 | 2,000 | Runs intermittently |
| Well pump (1/2 hp, 240V) | 1,000 | 2,000β3,000 | Deep-well pumps surge higher |
| Window AC (12,000 BTU) | 1,200 | 3,600 | Inverter units surge far less |
| Central AC (3-ton) | 3,500 | 8,000β10,000 | Soft-start kit cuts surge sharply |
| Microwave | 1,000 | 1,000 | Resistive, no meaningful surge |
| LED lighting (10 fixtures) | 100 | 100 | Negligible |
Two failure cases deserve names. First, a sump pump and furnace blower starting in the same second during a spring storm can stack surges a spreadsheet misses β sequence them or oversize slightly. Second, a refrigerator that's been off for hours draws a longer, harder surge when it restarts warm, so don't size to the label alone.
Portable, inverter, and standby: three product classes that solve different problems
The class of generator matters more than the wattage printed on the box, because each class has a different relationship between its rating and what it can actually deliver continuously.
| Class | Typical running watts | Fuel | Run time at half load | Real constraint |
|---|---|---|---|---|
| Portable open-frame | 3,500β12,000 | Gasoline | 8β12 hours | Noise, CO risk, manual refueling |
| Inverter portable | 2,000β7,500 | Gasoline/propane | 6β12 hours | Clean power, but surge headroom is thinner |
| Home standby | 10,000β26,000 | Natural gas or LP | Unlimited with fuel supply | Requires transfer switch, permit, pad |
| PTO or diesel | 10,000+ | Diesel/tractor | Varies | Cost, maintenance, fuel storage |
Home standby units are rated for continuous output and are installed with an automatic transfer switch, which is why they're the only class that comfortably covers a whole house. A 22 kW air-cooled standby is the common residential ceiling; larger homes step to 26 kW or liquid-cooled units. Those figures are manufacturer-published and vary by model β confirm on the maker's site rather than trusting a retailer's summary.
Portable units are rated differently. Many advertise "peak" watts that the unit can hold for seconds, and "running" watts that it can sustain. An inverter rated at 7,500 running watts may only tolerate a 9,000-watt surge β fine for a well pump, marginal for a 4-ton air conditioner without a soft start.
The third path is a manual transfer switch with a portable unit, which is the cheapest compliant route for essential-circuit backup. It also caps what you can power at the switch's circuit capacity, usually 6β10 circuits. That cap is the honest limit most buyers discover after purchase.
What a whole-house number actually looks like for four home profiles
Whole-house sizing is not one figure. It's a function of square footage, climate, and which appliances are electric. The four profiles below use NEC Article 220's optional method as the frame, with typical appliance draws.
| Home profile | Square footage | Heating/cooling | Typical whole-house standby size |
|---|---|---|---|
| Small gas-heated home | 1,200β1,600 | Window AC, gas furnace | 10β14 kW |
| Mid-size gas home | 2,000β2,500 | 3-ton central AC, gas heat | 18β22 kW |
| All-electric home | 2,000β2,500 | Heat pump, electric range | 22β26 kW |
| Large all-electric | 3,500+ | Two AC systems, electric everything | 26 kW+ or managed-load system |
Managed-load or load-shedding technology changes the arithmetic. A 22 kW standby paired with a load-management module can serve a home whose calculated load exceeds 22 kW by shedding the range or water heater while the compressor runs. Manufacturers publish which circuits their modules control β that's the specification to verify, not the marketing headline.
A worked example: a 2,400-square-foot gas-heated home with a 3-ton AC, well pump, and standard appliances calculates to roughly 19β21 kW under the optional method. A 22 kW unit with a 200-amp service-rated transfer switch covers it. Drop to 18 kW and the AC and well pump may not start simultaneously β acceptable if you accept the sequencing.
How to read a generator's spec sheet without getting fooled
Three numbers on the label do most of the work, and two numbers on the label are usually marketing. Running watts, surge watts, and the voltage configuration (120/240 split-phase) are the working figures. "Peak" watts and "maximum" watts are the soft ones.
Look for a continuous rating stated at a specific ambient temperature. Generator output derates as altitude rises and temperature climbs β a unit rated at 7,000 watts at sea level and 60Β°F may deliver meaningfully less at 5,000 feet or 100Β°F. Manufacturers publish derate tables; if a seller doesn't, that's a signal.
Total harmonic distortion matters for electronics and modern HVAC controls. Inverter generators typically publish THD under 3%, while open-frame units often run 5β15%. A furnace control board or a variable-speed heat pump is less tolerant than a refrigerator. If your backup plan includes either, ask for the THD figure.
Fuel type changes the wattage. Dual-fuel portables typically produce 10β15% fewer watts on propane than on gasoline β a real drop that can push a borderline unit below your surge requirement. Standby units are usually sold in natural gas and LP configurations with different ratings for each; verify the fuel you'll actually use.
Fuel, runtime, and the cost math nobody puts on the box
Runtime is where portable ownership gets expensive, and the arithmetic is straightforward once you have the numbers. A portable gasoline generator burns roughly 0.5 gallons per hour at half load for every 1,000 watts of output β so a 7,000-watt unit at half load (3,500 watts) consumes about 0.75β1.0 gallon per hour depending on the engine.
Run that forward. A three-day outage with a 7,000-watt portable running 12 hours a day at half load consumes roughly 27β36 gallons. At a national average gasoline price near $3.15 per gallon β the U.S. Energy Information Administration publishes weekly retail figures β that's $85β$115 for one event. Five outages a decade and the fuel bill alone approaches $500.
Home standby units on natural gas avoid the refueling problem entirely. Natural gas is billed per therm, and a 22 kW air-cooled unit at half load consumes roughly 2.5β3.5 therms per hour depending on the fuel's heating value and the unit's efficiency β manufacturers publish fuel-consumption tables per model at 50% and 100% load. At a residential gas rate near $1.20β$1.50 per therm (EIA publishes state averages monthly), a half-load day costs roughly $70β$125.
Those two cost figures aren't comparable in the way buyers assume. The standby costs more per hour to run but eliminates the 2 a.m. fuel run and the carbon monoxide risk of a portable placed too close to a window. That's the trade, and it's worth naming plainly.
Installation reality: permits, transfer switches, and the inspection that stops projects
Every permanently connected generator needs a transfer switch, and the transfer switch is what prevents backfeeding β the condition where generator power flows backward into utility lines and endangers line workers. The NEC requires it, and utilities enforce it.
Service-rated automatic transfer switches for a 200-amp service typically cost $600β$1,200 for the switch alone, and installation by a licensed electrician runs into the thousands depending on trenching, gas line work, and the concrete pad. Those prices vary by region and by year; treat them as order-of-magnitude and get local quotes.
Permits are the schedule driver. Most jurisdictions require an electrical permit for the transfer switch and a mechanical or gas permit for the fuel connection, and inspection happens before the utility approves the install. A project that looks like a two-week job often runs four to six weeks on permitting alone β a timeline worth knowing before storm season.
Portable setups avoid most of this. A cord-and-plug connection to a manual transfer switch still needs the switch installed, but the generator itself needs no permit. That's the pragmatic reason many homeowners choose a 7,500-watt portable plus a 10-circuit transfer switch over a standby: the compliance burden is smaller even though the convenience is lower.
Five sizing mistakes that lead to a generator that won't start your AC
These are the errors that show up after purchase, usually on the first hot outage.
1: Sizing to total nameplate watts. Adding every appliance label produces a number 40β60% higher than actual diversified load. Use the NEC optional method or a load calculator, not a sum of labels. 2: Ignoring the largest surge. A unit that covers running load but not the AC's locked-rotor surge will trip its breaker every time the compressor cycles. 3: Forgetting the well pump is 240 volts. Many small portables only deliver 120 volts on their household outlets. A 240-volt pump needs the twist-lock outlet and a generator that produces split-phase power. 4: Buying propane capacity without derating. A dual-fuel unit rated 7,500 watts on gasoline may produce 6,750 on propane β enough to miss a surge that was already marginal. 5: Skipping the soft-start kit. A soft-start on the AC condenser can cut starting current enough to let a smaller generator carry the load, often for less than the price difference between two generator sizes.
The fifth item is the highest-leverage fix on the list. Soft-start devices are widely available for residential condensers, and the manufacturer-published reduction in locked-rotor amps is the figure to check against your generator's surge rating.
Matching the answer to your situation: a decision rule
Use this rule rather than a single recommended size, because the right answer depends on which loads you refuse to lose.
If you need refrigeration, heat, lights, and internet during short outages, a 3,500β5,000-watt inverter portable plus a manual transfer switch covers it. If you have a well pump or central AC and want to run either, move to 7,500β12,000 watts and add a soft-start kit. If you want the house to behave normally β every circuit live, automatic start within seconds β a 14β26 kW home standby with an automatic transfer switch is the only class that delivers it.
Budget follows the class, not the wattage. A portable plus transfer switch is the low four figures; a standby install is commonly five figures once the switch, pad, gas line, permit, and labor are counted. Get two local quotes before committing, and confirm the transfer switch amperage matches your service panel.
One boundary worth stating: generator sizing touches electrical code, fuel connections, and carbon monoxide safety. This article is general educational information, not an electrical or safety code determination for your property. Have a licensed electrician review the load calculation and the transfer-switch installation, and follow the manufacturer's clearance and CO-warning instructions exactly β generator exhaust is lethal indoors and near windows.
FAQ
Can a 7,500-watt generator run a central air conditioner?
Often yes, but only with a soft-start kit installed on the condenser. A 3-ton unit drawing 3,500 running watts can surge to 8,000β10,000 watts without one, which exceeds a 7,500-watt unit's brief surge rating. With a soft start cutting locked-rotor current substantially, the same system becomes startable β verify the kit's published reduction against your generator's surge figure.
Do I add up every appliance's watts to size a generator?
No. Adding nameplate watts overstates load by roughly 40β60% because not every appliance runs simultaneously. The NEC Article 220 optional method applies demand factors instead. For a portable setup, list only the circuits you'll actually back up and apply the largest single surge β that's the working number.
What's the difference between running watts and surge watts on the label?
Running watts is continuous output the unit sustains indefinitely; surge watts is a brief overload capability, usually lasting seconds. Manufacturers sometimes print "peak" watts that exceed the surge rating, which is marketing rather than a usable specification. Size to running watts for total load and confirm surge watts clears your largest motor start.
Will a generator run on propane produce fewer watts than on gasoline?
Yes, typically 10β15% fewer. A dual-fuel portable rated 7,500 watts on gasoline may produce around 6,750 on propane. That derate can push a borderline unit below the surge requirement for an air conditioner or well pump, so size against the fuel you'll actually use during an outage.
How much fuel does a portable generator burn in a three-day outage?
Roughly 27β36 gallons for a 7,000-watt unit running 12 hours daily at half load, based on the common 0.5 gallons per hour per 1,000 watts rule of thumb. At the EIA's weekly retail average near $3.15 per gallon, that's $85β$115 for one event β before oil changes and storage costs.
Does a home standby generator need a permit?
Almost always. Most jurisdictions require an electrical permit for the transfer switch and a gas or mechanical permit for the fuel line, with inspection before utility approval. Timelines commonly run four to six weeks including permitting, which is why installers schedule standby work well before storm season.
Can I just plug a portable generator into a wall outlet?
Never. Backfeeding through a wall outlet sends power backward into utility lines and endangers line workers; it's also a code violation and a fire risk. The compliant path is a manual or automatic transfer switch installed by a licensed electrician, which isolates your panel from the grid before generator power flows.